Rockwell Automation Publication 1407-UM001G-EN-P - April 2013

33

Installation Chapter 2

Real-power Load Sharing

The load sharing terminals connect to a 0…5V DC, internally powered circuit.
The load sharing terminals are on TB7 and are labeled LS(+) and LS(-). Terminal
SHLD4 is provided to land the cable shield. Twisted, shielded cabling is required
for the load sharing connections.

Figure 23 - Real-power Load Sharing

Cross-current Compensation

The

Cross-current (reactive differential) Compensation Connection Diagram on

page 34

shows a typical connection diagram for three paralleled generators using

the 5 A sensing input range on the AC current input.

Make connections with 2.6 mm (10 AWG) copper wire for CT inputs.

The resistance of the cross-current CT wiring must be as low as possible. A loop
resistance less than 10% of the internal cross -current burden resistance of
1.0 

(1)

enables cross-current operation with negligible voltage droop. If the

CCCT loop resistance must be higher, adjust the CCCT gain or increase the
cross-current burden resistance. You can do those things by adding external
resistance to each CGCM unit in the loop.

The cross-current compensation terminals are on TB3 and are labeled ID(-) and
ID(+). One and five ampere range terminals are provided.

TB7

LS (+)
LS (-)
SHLD 4

TB 7

LS (+)
LS (-)
SHLD 4

TB 7

LS (+)
LS (-)
SHL D 4

CGCM 1

CGCM2

CGCM3

Ground shield at
only one point.

(1) Series C devices have internal 1  resistor. Earlier devices can require an external resistor.