Chapter 7

Troubleshooting

Table 23 - Compensation Modes - Droop

Symptom

Most Likely Cause

Diagnostic Action

Corrective Action

Voltage does not change with

changes in reactive load while not

connected to the grid

Droop not selected/active

Check tag Droop_Ened

If not active, check/correct logic for

mode selection

Cross current mode is

enabled/selected

Check Droop_CCCT_Select tag

If active, check/correct logic for

mode selection

Metering error

See Metering troubleshooting

See Metering troubleshooting

Reactive power does not change

with adjustments to the voltage

setpoint while connected to the grid

Droop not selected/active

Check tag Droop_Ened

If not active, check/correct logic for

mode selection

PF or VAR control enabled/selected

Check tag PF_VAR_Control

If active, check/correct logic for

mode selection

Metering error

See Metering troubleshooting

See Metering troubleshooting

Voltage and / or reactive load is

unstable when operating in droop

AVR Gains misadjusted

Check voltage stability when

operating isolated from load and if

possible in constant voltage control

Calculate/correct AVR gains if

required

Metering error

See Metering trouble shooting

See Metering trouble shooting

Table 24 - Compensation Modes - Cross Current

Symptom

Most Likely Cause

Diagnostic Action

Corrective Action

VARs share but not equally; even

when the system load changes

Gain mis-adjustment

Check CCCT Gain

Correct as required

CT or input impedance mismatch

Verify CT selection and measure

input impedance to each AVR

Correct or replace CTs as required.

Add resistors as required to match

AVR input resistance

VARs do not share at all and when a

voltage adjust is made, nothing

happens

Cross current mode is not

enabled/selected

Check Droop_CCCT_Select tag

and kVAR_LS-En tag

If not active, check/correct logic for

mode selection

Gain misadjustment

Check CCCT Gain

Correct as required

Wiring error

Measure voltage at ID+/- terminal

and adjust reactive power/voltage

Correct wiring as required if voltage

signal from CCCT circuit is not

observed