Proportional Gain Kp - Sets the proportional gain, which determines the

characteristic of the dynamic response to changes in generator voltage. If
the transient response has too much overshoot, decrease Kp. If the
transient response is too slow, with little or no overshoot, then increase Kp.
The tag AVR_FCR_Kp in the Unscheduled Write table stores this
parameter.

Integral Gain Ki – Sets the integral gain. If the time to reach steady state is

too long, increase Ki. The tag AVR_FCR_Ki in the Unscheduled Write
table stores this parameter.

Derivative Gain Kd – Sets the derivative gain. To improve the transient

response to a step change, increase Kd. If there is too much jitter in the
steady-state voltage, decrease Kd. The tag AVR_FCR_Kd in the
Unscheduled Write table stores this parameter.

Time Constant Td - The filtering time constant, Td, is used to remove the

noise effect on the numerical differentiation. The tag AVR_FCR_Td in
the Unscheduled Write table stores this parameter, expressed in seconds.

FCR Overall Gain Kg - Sets the overall gain of the voltage regulator in

FCR mode. It determines the characteristic of the dynamic response to a
change in the CGCM unit output current. The tag FCR_Kg in the
Unscheduled Write table stores this parameter.

AVR Overall Gain Kg – Sets the overall gain of the voltage regulator in

AVR mode. It determines the characteristic of the dynamic response to a
change in the voltage of the generator. The tag AVR_Kg in the
Unscheduled Write table stores this parameter.

Voltage Matching Gain – This parameter is not used. Set to zero. The tag

V_Match_Gain

in the Unscheduled Write table stores this parameter.