Field current regulator – Rockwell Automation 1407-CGCM Combination Generator Control Module User Manual

Page 191

Advertising
background image

Rockwell Automation Publication 1407-UM001G-EN-P - April 2013

191

CGCM Unit Math Models Appendix B

Field Current Regulator

Per-unit Block Diagram for Rotating Rectifier Excitation System

shows the

model of the CGCM field current regulator used with a brush-type rotating
exciter. V

P

is the input from the power source for the excitation system.

Typical value for T

A

is 0. The forcing limit V

RLMT

is related to the power-input

voltage (V

P

) to the CGCM, the exciter field voltage (V

R

) and the programmed

gain (K

G

) in this equation.

V

RLMT

= 1.4*V

P

/ V

R

The gain K

G

is used for compensating variations in system configuration

dependent gains such as power input voltage.

The PI gains K

P

and K

I

are the same as the PI gains K

P

and K

I

for the voltage

regulator. The PID gains can be obtained from the PID Calculator software
available from Rockwell Automation.

Figure 69 - Per-unit Block Diagram for Rotating Rectifier Excitation System

V

RLMT

(V

p

0.00013)

-V

RLMT

(V

p

0.00013)

Advertising