Rockwell Automation 1407-CGCM Combination Generator Control Module User Manual

Page 57

Advertising
background image

Rockwell Automation Publication 1407-UM001G-EN-P - April 2013

57

CGCM Unit Operation Chapter 3

Loss of Excitation Power (PMG) (27)

If voltage to the PMG excitation power inputs falls below 10V AC for
approximately 400 ms or more, a Loss of Excitation power fault occurs. When
single phase PMG is selected, the CGCM unit senses phases A and C for this
function. This function is disabled when Shunt excitation is selected, the
EngineIdle

tag is set, or the host Logix controller is in Program mode. If this fault

occurs, tag LossPMGFlt = 1 in the Scheduled Read table.

Reverse VAR (40Q)

When the Reverse VAR level exceeds the characteristic curve for an amount of
time you set, a Reverse VAR fault occurs. The characteristic curve is a line that
begins at the pickup setting you defined at zero real power and extends toward
positive reactive power at an angle of 8°. Once the VARs increase above the
threshold, the Reverse VAR fault timer is reset. If this fault occurs, the CGCM
unit shuts down excitation and sets tag RevVARFlt = 1 in the Scheduled Read
table.

The

Reverse VAR Characteristic

graph shows more details.

Figure 35 - Reverse VAR Characteristic

1.0

0.8

0.6

0.4

0.2

0.0

-0.2

-0.4

-0.6

-0.8

-1.0

0.0

0.2

0.4

0.6

0.8

1.0

1.2

1.4

Lagging

Leading

Reactive Power

, per Unit

Generator

Characteristic

Curve

Trip Region

Reverse VAR

Trip Setting

Real Power, per Unit