Rockwell Automation 1407-CGCM Combination Generator Control Module User Manual

Page 154

Advertising
background image

154

Rockwell Automation Publication 1407-UM001G-EN-P - April 2013

Chapter 7

Troubleshooting

Voltage output is greater than

setpoint

AVR not selected / enabled

Check excitation AVR select

Correct Logix controller logic or I/O

as required

Wiring error

Check wiring for excitation current

output, VT inputs, fuses open,

grounding, and PMG/supply

Correct wiring as required

Gain mis-adjusted

Check gains entered into CGCM unit

configuration

Calculate / adjust as required

Excitation limiting active

Check UEL active input

Correct UEL configuration or change

operating point

Droop compensation is driving up

the voltage

Check Droop Enable

Adjust/disable droop compensation

Voltage is erratic or unstable

Gain mis-adjusted

Check gains entered into CGCM unit

configuration

Calculate / adjust as required

Wiring error

Check wiring for excitation current

output, VT inputs, fuses open,

grounding, and PMG/supply

Correct wiring as required

Prime mover is unstable

Check prime mover governor

operation

Correct as required

Excitation limiting active

Check UEL/OEL active input

Correct UEL/OEL configuration or

change operating point

Table 20 - Excitation Control - AVR

Symptom

Most Likely Cause

Diagnostic Action

Corrective Action