Chapter 3

CGCM Unit Operation

Over-excitation Limit

Over-excitation limiting (OEL) operates in all modes except FCR. The CGCM
unit senses and limits the field current to prevent field overheating. When the
limit is reached, the limiter function overrides AVR, VAR, or Power Factor
modes to limit field current to the preset level. OEL operates in the area above
the Field Winding Heating Limitation curve in the generator capability curve.

The generator operates in one of two different states, offline or online. The
generator is offline when it is operating in a constant-voltage mode. The CGCM
unit is considered online if any of these modes are enabled:

Droop (reactive power) compensation
Cross current compensation
Line drop compensation

Two OEL current levels, high and low, are defined for offline operation as shown
in the graph below. The generator can operate continuously at or below the low
OEL current level and for a time at the high OEL current level that you
configure.

Figure 32 - Offline Over-excitation Limiting

Three OEL current levels, high, medium, and low are defined for online
operation as shown in the graph below. The high and medium current levels can
be maintained only for time periods you define. The generator can operate
continuously at or below the low OEL current level.

Figure 33 - Online Over-excitation Limiting

FIELD

C

URRENT

TIME IN SECONDS

High

Current

Time

CONTINUOUS

0…10 seconds

Low

Current

Level

0…15 A dc

High

Current

Level

0…30 A dc

FIELD CURRENT

TIME IN SECONDS

High

Current

Time

0…10 seconds

CONTINUOUS

Medium

Current

Time

0…120 seconds

Low

Current

Level

0.0…15 A dc

Medium

Current

Level

0.0… 20 A dc

High

Current

Level

0.0…30 A dc