Troubleshooting Chapter 7

Current does not read correctly

Configuration errors

Observe CT configuration

parameters and to verify they reflect

desired/ expected CT ratios

Correct configuration to match

expected CT wiring

Wiring errors

Observe each phase, and average

current indication. Each phase

current indicated is approximately

equal and the average represents

the average of the three. If all low or

high indicate ratio error, if one or

two are low or high indicate

polarity, grounding, or disconnection

Correct phase rotation, polarity, or

grounding, as applicable. Confirm

the correct CT inputs are used

Measure signal at CGCM unit

terminals

If current indicated corresponds to

measured value, correct CT wiring.

If current indicated does not

correspond to measured current, see

configuration errors. If configuration

is correct, replace CGCM unit

KW does not read correctly

CT Wiring error

See Current troubleshooting above.

Observe kVA indicated. If kVA and

voltage are correct, verify CT phase

rotation

See Current troubleshooting above

VT wiring error

See Voltage troubleshooting above.

Then observe kVA indicated. If kVA

and voltage are correct, see CT

wiring troubleshooting

See Voltage troubleshooting above

kVAR does not read correctly

CT Wiring error

See Current troubleshooting above.

Observe kVA indicated. If kVA and

voltage is correct, verify CT phase

rotation

See Current troubleshooting above

VT wiring error

See Voltage troubleshooting above.

Then observe kVA indicated. If kVA

and voltage are correct, see CT

wiring troubleshooting

See Voltage troubleshooting above

Table 30 - Metering

Symptom

Most Likely Cause

Diagnostic Action

Corrective Action