Chassis, Ground, Ac voltage and current sensing – Rockwell Automation 1407-CGCM Combination Generator Control Module User Manual

Page 20

Advertising
background image

20

Rockwell Automation Publication 1407-UM001G-EN-P - April 2013

Chapter 2

Installation

Chassis

Ground

The terminal labeled CH GND, on TB4, is the chassis ground. Ground studs are
also provided on the lower part of the mounting flanges and are internally
connected to the CH GND terminal. Connect chassis ground to earth ground
with minimum 2.6 mm

2

(10 AWG) copper wire attached to either stud on the

lower part of either side of the unit and to the CH GND terminal with 1.6 mm

2

(14 AWG) copper wire. When installed in a system with other CGCM units, use
a separate lead to the ground bus from each unit.

AC Voltage and Current Sensing

The CGCM unit supports generator and bus voltage sensing and generator
current sensing.

Generator and Bus Voltage Sensing

CGCM units accept single-phase or 3-phase generator and bus voltage sensing
input with nominal voltages of 120 or 208V AC.

Refer to

Terminal Block Label Description

on

page 15

for possible wiring

configurations.

The terminals found on TB5 provide connections for generator voltage sensing
and are labeled V GEN A, V GEN B, V GEN C, and V GEN N. The terminals
found on TB6 provide connections for bus voltage sensing and are labeled V BUS
A, V BUS B, V BUS C, and V BUS N. The connection examples below show
typical connections for various generator and bus connection schemes.

The CGCM unit supports these generator connection schemes:

Single-phase
Delta or Two-transformer Open Delta
Three-wire Wye
Four-wire Wye

The CGCM supports these bus connection schemes:

Single-phase
Delta or Two-transformer Open Delta
Three-wire Wye
Four-wire Wye
Dual Breaker, Single-phase only