86

Rockwell Automation Publication 1407-UM001G-EN-P - April 2013

Chapter 4

CGCM Unit Configuration

The tags listed below determine the points shown in the UEL

configuration diagrams below. These tags are in the configuration table
and are set by the like-named fields in the UEL tab. Configure the VAR
and Watt tags with increasing real power values in point 1 through point

x.

These tags define the curve breakpoints. As shown, the curve continues
horizontally left from point 1 and vertically up from point 5. The tags are
expressed in Watts or VARs respectively.

Point 1 is defined by tags UEL_Curve_W_Pt1 and
UEL_Curve_VAR_Pt1

Point 2 is defined by tags UEL_Curve_W_Pt2 and
UEL_Curve_VAR_Pt2

Point 3 is defined by tags UEL_Curve_W_Pt3 and
UEL_Curve_VAR_Pt3

Point 4 is defined by tags UEL_Curve_W_Pt4 and
UEL_Curve_VAR_Pt4

Point 5 is defined by tags UEL_Curve_W_Pt5 and
UEL_Curve_VAR_Pt5

Validate and Graph button – Updates the graph in the UEL tab after

entering new values.

Related Parameters

• UEL_En tag in the Output table

1

2

3

4

5

Real Power, Watts

Reactive Power

, V

ARs