System:communicate:rs232:databit, System:communicate:rs232:flowcrl, System:communicate:rs232:paritybit – RIGOL DP832A User Manual

Page 141: System:communicate:rs232:databit -117, System:communicate:rs232:flowcrl -117, System:communicate:rs232:paritybit -117

Advertising
background image

Chapter 2 Command System

RIGOL

DP800 Programming Guide

2-117

:SYSTem:COMMunicate:RS232:DATABit

Syntax

:SYSTem:COMMunicate:RS232:DATABit {5|6|7|8}
:SYSTem:COMMunicate:RS232:DATABit?

Description

Set the data bit of the RS232 interface.
Query the data bit of the RS232 interface.

Parameter

Name

Type

Range

Default

{5|6|7|8}

Discrete

5|6|7|8

8

Return Format

The query returns 5, 6, 7 or 8.

Example

:SYST:COMM:RS232:DATAB 8 /*Set the data bit of the RS232 interface to 8*/
:SYST:COMM:RS232:DATAB? /*Query the data bit of the RS232 interface and the

query returns 8*/

:SYSTem:COMMunicate:RS232:FLOWCrl

Syntax

:SYSTem:COMMunicate:RS232:FLOWCrl {ON|OFF}
:SYSTem:COMMunicate:RS232:FLOWCrl?

Description

Enable or disable the hardware flow control.
Query the status of the hardware flow control.

Parameter

Name

Type

Range

Default

{ON|OFF}

Bool

ON|OFF

OFF

Explanation

This power supply uses RTS/CTS hardware flow control mode. The instrument

monitors the status of the CTS pin. When the status is "True", the instrument sends

data; when the status is "False", the instrument stops sending data. The instrument

sets the CTS pin to "False" when the input buffer area is almost full and sets the CTS

pin to "True" when the input buffer area is available again.

Return Format

The query returns ON or OFF.

Example

:SYST:COMM:RS232:FLOWC ON /*Enable the hardware flow control*/
:SYST:COMM:RS232:FLOWC? /*Query the status of the hardware flow control

and the query returns ON*/

:SYSTem:COMMunicate:RS232:PARItybit

Syntax

:SYSTem:COMMunicate:RS232:PARItybit {NONE|ODD|EVEN}
:SYSTem:COMMunicate:RS232:PARItybit?

Description

Set the parity mode.
Query the current parity mode.

Parameter

Name

Type

Range

Default

{NONE|ODD|EVEN}

Discrete

NONE|ODD|EVEN

NONE

Explanation

NONE, ODD and EVEN represent to set the parity mode to "None", "Odd" and

"Even" respectively.

Return Format

The query returns NONE, ODD or EVEN.

Example

:SYST:COMM:RS232:PARI ODD /*Set the parity mode to odd*/
:SYST:COMM:RS232:PARI? /*Query the current parity mode and the query

returns ODD*/

Advertising