<2. Installation, Wiring and Piping>

2-6

IM 11T3E1-01E

2.2.2

GD402T (FM Explosion-proof Approval)

Sealing Fitting

Conduit

475 mm (18") Max.

NON-HAZARDOUS

LOCATIONS

HAZARDOUS

LOCATIONS

GD402T

F0202.ai

Figure 2.4

1. GD402T Gas density converter for use in hazardous (classified) locations:

• Explosion-proof for Class I, Division 1, Groups B, C and D;

Dust Ignition-proof for Class II, III, Division 1, Groups E, F and G

• Enclosure Rating:

NEMA 4X

• Temperature Code:

T6

• Ambient Temperature: -10 to 55°C

2. Wiring

• All wiring shall comply with National Electrical Code ANSI/NFPA 70 and Local Electrical

Codes.

WARNING

Seal all conduits within 475 mm (18 inches). Refer to Figure 2.4.

3. Operation

• Note a warning label worded as follows.

WARNING

Open circuit before removing cover.

• Take care not to generate mechanical spark when access to the instrument and

peripheral devices in hazardous locations.

4. Maintenance and Repair

• The instrument modification or parts replacement by other than authorized representative

of Yokogawa Electric Corporation is prohibited and will void the approval of Factory Mutual

Research Corporation.