<2. Installation, Wiring and Piping>

2-20

IM 11T3E1-01E

2.4.6

Cables Wired to the Ground

When using the GD40R detector in an area requiring explosion protection, BE SURE to ground it

as per the Class A Grounding Standard using a conductor of at least 2 mm

2

in nominal thickness.

Also BE SURE to ground the GD402 converter as per the Class D Grounding Standard.
In the case of using GD40T detector, Intrinsically Safe Grounding shall comply with National

Electrical Code ANSI / NFPA 70 and Local Electrical Codes.
In the case of using GD40V detector, Intrinsically Safe Grounding shall comply with Canadian

Electrical Code and Local Electrical Codes.
Use No. 26 internal wiring terminals or the grounding terminals of the converter. (The appropriate

tightening torque for the internal wiring terminals is 0.4 N·m). When using the detector’s ground-

ing terminals, attach M4 crimp terminals to the ends of the grounding cables. When crimping the

terminals, use tools that fit the terminals.

Earth cable

F0221.ai

Terminal

Joining advice of Converter

case ground terminal

Converter case

Ground wiring

crimp terminal

Lock washer

Ground terminal

Earthing of internal wiring terminal

Earthing of enclosure wiring terminal

24

26

25

L

N

Figure 2.17 Power and Ground Wiring