B.4.5

Checking the data

Permitted value ranges

Transferred parameters and values are checked by the
SFC−LACI before being accepted.

Note
In the case of invalid parameters or values, an error
message will not appear in the response; rather, the
received value will always be returned (Echo).

Recommendation:
Check that values have been written correctly by
downloading the current contents of the object with a
subsequent Read command. The higher level controller must
compare the sent command with the Echo" from the
SFC−LACI and check the checksum.

Note
The following applies when writing the objects:

Ĉ Discrete values (values from a value list):

an invalid value will not be accepted; the previously
valid value will be retained.

Ĉ Continuous values (e.g. lengths, speeds, etc.): an imperĆ

missible value will be limited to the nearest permitted
value.

Error messages

If there are errors in the commands (e.g. syntax errors,
transmission errors), the value <0x00FF> will be transmitted
(object 2FF0h) instead of the usual reply. Possible causes:

ć

incorrect initial character, separating character or empty
character

ć

incorrect hex digit

ć

incorrect value type.