3. Installation
3−18
Festo P.BE−GDCP−SFC−LACI−PB−E N en 0812NH
3.7.2
Field bus baud rate and field bus length
Note
The maximum permitted field bus segment lengths depend
on the baud rate used.
·
Note the maximum permitted segment length (cable
length without repeater), if you connect the SFC−LACI to
a field bus segment.
·
Avoid branch lines.
·
Note the information in the manufacturer’s manuals for
your controller.
The baud rate is defined by the master and is recognized
automatically by the SFC−LACI.
Baud rate
Maximum segment length
9.6; 19.2; 45.45; 93.75 kBaud
1200 m
187.5 kBaud
1000 m
500 kBaud
400 m
1500 kBaud
200 m
1.5 ... 12 MBaud
100 m
Tab. 3/9:
Maximum field bus segment lengths for
PROFIBUS−DP depending on the baud rate