3. Installation

3−17

Festo P.BE−GDCP−SFC−LACI−PB−E N en 0812NH

3.7

Connecting the field bus

3.7.1

Field bus cable

Note
Faulty installations or high transmission rates may cause
data transmission errors as a result of signal reflections
and attenuations.
Transmission errors can be caused by:

Ĉ missing or incorrect terminating resistor

Ĉ incorrect screened connection.

Ĉ branches

Ĉ transmission over long distances.

Ĉ unsuitable cables.

Observe the cable specifications. Refer to the manual for
your control system for information on the type of cable to
be used.

Note
If the SFC−LACI is installed in a machine on a movable
mounting, the field bus cable must be provided with strain
relief on the moving part of the machine. Please also
observe the relevant regulations in ENĂ60204 part 1.

Use a twisted screened 2−core cable for the field bus in
accordance with PROFIBUS specifications (EN 50170,
cableĂtype A):

Surge impedance:

135 ... 165 ġ (3 ... 20 MHz)

Capacitance per unit length:

< 30 nF/km

Loop resistance:

< 110 ġ/km

Core diameter:

> 0.64 mm

Wire cross section:

> 0.34 mm