3. Installation
3−23
Festo P.BE−GDCP−SFC−LACI−PB−E N en 0812NH
3.8
Bus termination with terminating resistors
Note
If the SFC−LACI is at the start or end of the field bus
segment, a bus terminator is required.
·
Fit a bus termination to both ends of a bus segment.
Recommendation:
Use the ready−to−use field bus plugs from Festo for the bus
termination. A suitable resistor network is incorporated in the
housing of this plug (see Fig. 3/5).
Received/transmitted data P
(data cable B)
Received/transmitted data N
(data cable A)
390 ġ
390 ġ
220 ġ
Pin 6: Supply voltage
Pin 5: Data reference potential
Pin 3
Pin 8
120 nH
120 nH
Fig. 3/5:
Circuit diagram for bus termination network for
cable type A as per ENĂ50170 (switch in Festo
fieldĂbus plug set to ON)