Wiring of the standard device

Standard devices in the power range 0.37 ... 11 kW
Motor connection

5

5.4
5.4.6

l

5.4−10

EDSVS9332S EN 6.0−07/2013

PE

PE

U

U

V

V

W

W

T1

T1

T2

T2

U, V, W
T1, T2

0.5...0.6 Nm
4.4...5.3 lb-in

U, V, W
T1, T2

0.5...0.6 Nm
4.4...5.3 lb-in



‚

2

2

3

3

1

1

0

0

9300std011

Fig. 5.4−6

Motor connection with PTC thermistor or thermal contact (NC contact)

 0 Motor connection with Lenze system cable with integrated control

cable for the motor temperature monitoring

1 Shield sheet

Clamp entire shield and shield of the control cable for the motor
temperature monitoring with the straps. If required, fix by means of
cable tie.

‚ 0 Motor cable connection and separate control cable for the motor

temperature monitoring

1 Shield sheet

Clamp shield of the motor cable and shield of the cable for the motor
temperature monitoring with the straps. If required, fix by means of
cable tie.

2 U, V, W

Motor cable connection
Check the correct polarity. Observe maximum length of the motor cable. Use
wire end ferrules for flexible cables.
Max. connectable cable cross−section: 4 mm

2

, with pin−end connector

> 4 mm

2

3 T1, T2 for motor temperature monitoring

Cable connection for PTC thermistors or thermal contacts (NC contacts)

)

Note!

ƒ

We recommend to use Lenze system cables for wiring.

ƒ

For self−made cables only use cables with shielded cores
twisted in pairs.

Motor with KTY thermal
sensor