Configuration

Code table

8

8.4

l

8.4−10

EDSVS9332S EN 6.0−07/2013

IMPORTANT

Possible settings

Code

Selection

Lenze

Designation

No.

C0169

g corresponding mains switch−on time

List of the times when the faults occurred
under C0168 (based on C0179)

1 FAILTIME ACT

Currently active fault

2 FAILTIME OLD1

Last fault

... ...

...

8 FAILTIME OLD7

Last but six fault

C0170

g corresponding mains switch−on time

List of how often the faults have occurred
consecutively under C0168
History buffer

1 COUNTER ACT

Currently active fault

2 COUNTER

OLD1

Last fault

... ..

...

8 COUNTER

OLD7

Last but six fault

C0172

s

OV REDUCE

0

0

{10 V}

100 OV reduce

Threshold for activating the brake torque
reduction before OU message

C0173

s

UG LIMIT

1

DC−bus voltage thresholds
Check during commissioning and adapt if
necessary!
All drive components in the interconnection
must have the same thresholds!

0

Mains<400V +−brake LU=285V,
OU=770V−755V

Operation on mains <400 V with or without
braking unit

1

Mains=400V +−brake LU=285V,
OU=770V−755V

Operation on 400 V mains with or without
braking unit

2

Mains=460V +−brake LU=328V,
OU=770V−755V

Operation on 460 V mains with or without
braking unit

3

Mains=480V −brake LU=342V,
OU=770V−755V

Operation on 480 V mains without braking
unit

4

Mains=480V +−brake LU=342V,
OU=800V−785V

Operation on 480 V mains with braking unit

C0178 OP TIMER

g 0

{1 s}

4294967295 Elapsed−time meter

l

Time when the controller was enabled

C0179 MAINS TIMER

g 0

{1 s}

4294967295 Power−on time meter

l

Time during which the mains was
switched on

C0182 TI S−SHAPED

20.00 0.01

{0.01 s}

50.00 NSET

T

i

time of the S−shaped ramp function

generator
(determines the shape of the S curve)

l

Low values

Þsmall S rounding

l

High values

Þlarge S rounding