Wiring of the standard device – Lenze EVS9332xS User Manual

Page 123

Advertising
background image

Wiring of the standard device

Standard devices with a power of 45 kW
Mains connection, DC supply

5

5.6
5.6.3

l

5.6−4

EDSVS9332S EN 6.0−07/2013

PE

+UG

-UG

L1

L2

L3

3

0

1

2

L1, L2, L3
+U , -U
PE

G

G

M8
15 Nm
132 lb-in

}

+

PE

9300vec126

Fig. 5.6−2

Mains connection, DC supply for 45 kW controller

0 PE stud

Connect PE cable with ring cable lug

1 Conductive surface

2 Shield clamp

Place shield with large surface on control cabinet mounting plate and fasten
with shield clamp (shield clamp is not part of the scope of supply)
To improve the shield connection, also place the shield on the PE stud

3 Mains and DC bus connection

L1, L2, L3: Connection of mains cable with ring cable lugs
+U

G

, −U

G

: Connection of DC−bus components or connection of the controller

in the DC−bus system (see system manual)