Mounting in "cold plate" technique, Installing of the standard device – Lenze EVS9332xS User Manual

Page 55

Advertising
background image

Installing of the standard device

Standard devices in the power range 0.37 ... 11 kW
Mounting in "cold plate" technique

4

4.1
4.1.4

l

4.1−4

EDSVS9332S EN 6.0−07/2013

4.1.4

Mounting in "cold plate" technique

The drive controllers can be mounted in ˜cold plate˜ technique, e.g. on
collective coolers. For this purpose, the drive controllers of type EVS93xx−CSx
must be used.

Mounting material required from the scope of supply:

Description

Use

Quantity

EVS9321−CS
EVS9322−CS

EVS9323−CS
EVS9324−CS

EVS9325−CS
EVS9326−CS

Fixing bracket

Controller fixing

2

2

2

Sheet metal screw
3.5 × 13 mm (DIN 7981)

Mounting the fixing
bracket to the controller

6

6

6

The following points are important for safe and reliable operation of the
controller:

ƒ Good thermal connection to the cooler

– The contact surface between the collective cooler and the controller

must be at least as large as the cooling plate of the controller.

– Plane contact surface, max. deviation 0.05 mm.
– When attaching the collective cooler to the controller, make sure to

use all specified screw connections.

ƒ Observe the thermal resistance R

th

given in the table. The values are

valid for controller operation under rated conditions.

9300

Cooling path

Power to be dissipated

Heatsink − environment

Type

P

v

[W]

R

th

[K/W]

EVS9321−CS

24

1.45

EVS9322−CS

42

0.85

EVS9323−CS

61

0.57

EVS9324−CS

105

0.33

EVS9325−CS

180

0.19

EVS9326−CS

360

0.10

ƒ The rated data and the derating factors at increased temperature also

apply to the ambient temperature of the drive controllers.

ƒ Temperature at the cooling plate of the drive controller: max. 75 °C.

Requirements for collective
coolers

Ambient conditions

Advertising
This manual is related to the following products: