Configuration, Code table – Lenze EVS9332xS User Manual

Page 249

Advertising
background image

Configuration

Code table

8

8.4

l

8.4−8

EDSVS9332S EN 6.0−07/2013

IMPORTANT

Possible settings

Code

Selection

Lenze

Designation

No.

C0116

s

® Selection list 2 Signal configuration of the free digital

outputs
Free digital outputs can only be evaluated
when they are linked to automation
interfaces.

1 FDO−00

1000 FIXED0

... ...

...

...

32 FDO −31

1000 FIXED0

C0117

s

®

® Selection list 2 Signal configuration DIGOUT

à

Depending on C0005

1 DIGOUT1

15000 DCTRL−TRIP

X5/A1

2 DIGOUT2

10650 CMP1−OUT

X5/A2

3 DIGOUT3

500

DCTRL−RDY

X5/A3

4 DIGOUT4

5003 MCTRL−MMAX

X5/A4

C0118

0
1

HIGH active
LOW active

Terminal polarity DIGOUT

1 DIGOUT1 POL

1

X5/A1

2 DIGOUT2 POL

1

X5/A2

3 DIGOUT3 POL

0

X5/A3

4 DIGOUT4 POL

0

X5/A4

C0120 OC6 LIMIT

0

00

{1 %}

120 Threshold for the I

2

× t monitoring (motor).

l

0 = I

2

× t monitoring switched off

l

I

2

× t > C0120

ð trip OC6

C0121 OH7 LIMIT

150

45

{1 °C}

150 Temperature for OH7

Threshold for motor temperature warning

C0122 OH4 LIMIT

85

45

{1 °C}

85 Temperature for OH4

Warning threshold − heatsink temperature

C0125 BAUD RATE

0

0
1
2
3
4

9600 baud
4800 baud
2400 baud
1200 baud
19200 baud

LECOM baud rate
LECOM baud rate for 2102 accessory module

C0126 MONIT CE0

3

0
2
3

TRIP
Warning
Off

CE0monitoring
Configuration of communication error
monitoring with CE0 automation interface

C0127 OC8 LIMIT

0

0

{1 %}

120 Threshold for the I

2

× t advance warning

(motor).

l

0 = I

2

× t warning switched off

l

I

2

× t > C0127

ð OC8 fault message

(response set in C606)

C0128 TAU MOTOR

5.0

0.1

{0.1 min}

50.0 Thermal time constant of the motor

The time constant is required for calculating
the I

2

× t disconnection.

C0130 ACT TI

g

NSET
Active T

i

times of NSET

C0134 RFG CHARAC

0

0
1

Linear
S−shaped

NSET
Ramp function generator characteristic for
main setpoint

C0135 CONTROL

WORD

0

0

{1}

65535 Control word

Device control word for LECOM−A/B/LI or
keypad.

C0136

g

1 CTRLWORD

C135

Control word C135

2 CTRLWORD

CAN

Control word CAN

3 CTRLWORD AIF

Control word AIF

Advertising