Safety engineering

Operating mode

11

11.2

l

11.2−1

EDSVS9332S EN 6.0−07/2013

11.2

Operating mode

X11/34

X11/33

X11/K32

X11/K31

X5/28

5 V

µC

PWM

PWM

-

~

U

V

W



ƒ

‚

DIGOUT

K

SR

9300vec100

Fig. 11.2−1

Internal connection of the "Safe torque off" function with 3 electrically isolated
circuits

Area

:

Pulse inhibit via safety relay K

SR

; forcibly guided feedback for

monitoring the safety relay

Area

‚:

Controller inhibit (X5/28), optional feedback via a digital output
(DIGOUT)

Area

ƒ:

Power output stage

The "Safe torque off" status is activated via two different disconnecting
paths which are independent of each other:

1. disconnecting path: Pulse inhibit via safety relay K

SR

(terminal X11/33,

X11/34)

ƒ In the case of LOW level at terminals X11/33, X11/34, the safety relay

K

SR

is deactivated.The driver supply of the power section drivers is

interrupted. The inverter no longer receives pulses.

ƒ The disconnection of the safety relay K

SR

has to be monitored

externally, so that a failure of this disconnecting path can be detected.
X11/K31, X11/K32 is a forcibly guided break contact, i. e. if the safety
relay K

SR

has been deactivated ("Safe torque off" activated), the

contact is closed.

2. disconnecting path: Controller inhibit by input signal at terminal X5/28

ƒ The input signal at X5/28 is fed to the microcontroller system and the

PWM unit. In the case of LOW level at terminal X5/28, the output of
pulses to the inverter is inhibited in the microcontroller system.

ƒ The disconnecting path "Controller inhibit" can be evaluated optionally

via a digital output. Further information can be gathered from the
chapter "Functional test" (

11.5−1).

"Safe torque off" is activated if both disconnecting paths are on LOW level.