Mounting in "cold plate" technique, Installing of the standard device – Lenze EVS9332xS User Manual

Page 61

Advertising
background image

Installing of the standard device

Standard devices in the power range 15 ... 30 kW
Mounting in "cold plate" technique

4

4.2
4.2.4

l

4.2−4

EDSVS9332S EN 6.0−07/2013

4.2.4

Mounting in "cold plate" technique

The drive controllers can be mounted in ˜cold plate˜ technique, e.g. on
collective coolers. For this purpose, the drive controllers of type EVS93xx−CSx
must be used.

The following points are important for safe and reliable operation of the
controller:

ƒ Good thermal connection to the cooler

– The contact surface between the collective cooler and the controller

must be at least as large as the cooling plate of the controller.

– Plane contact surface, max. deviation 0.05 mm.
– When attaching the collective cooler to the controller, make sure to

use all specified screw connections.

ƒ Observe the thermal resistance R

th

given in the table. The values are

valid for controller operation under rated conditions.

9300

Cooling path

Power to be dissipated

Heatsink − environment

Type

P

v

[W]

R

th

[K/W]

EVS9327−CS

410

0.085

EVS9328−CS

610

0.057

ƒ The rated data and the derating factors at increased temperature also

apply to the ambient temperature of the drive controllers.

ƒ Temperature at the cooling plate of the drive controller: max. 75 °C.