Troubleshooting and fault elimination

System error messages

General error messages

9

9.3

9.3.1

l

9.3−5

EDSVS9332S EN 6.0−07/2013

Remedy

Cause

Description

Fault message

Remedy

Cause

Description

Display

No.

x089

PL

Error during rotor position
adjustment (the error is saved
with mains failure protection)

l

The rotor position adjustment
was cancelled.

l

During rotor position
adjustment with an absolute
value encoder the error Sd7 or
SD8 occurred.

Repeat rotor position adjustment.

^ 6.8−1

Note: After an Sd7 fault it is
absolutely required to carry out
another rotor position
adjustment. Otherwise the drive
may carry out uncontrolled
movements after controller
enable. The drive must not be
commissioned without a
successfully executed rotor
position adjustment!

x091

EEr

External monitoring has been
triggered via DCTRL.

A digital signal assigned to the
TRIP−SET function has been
activated.

l

Check external encoder.

l

Switch off the monitoring
(C0581 = 3).

0105

H05

Internal fault (memory)

Contact Lenze.

0107

H07

Internal fault (power stage)

During initialisation of the
controller, an incorrect power
stage was detected.

Contact Lenze.

x110

H10

Heatsink temperature sensor
error

Sensor for detecting the heatsink
temperature indicates undefined
values.

l

Contact Lenze.

l

Switch off the monitoring
(C0588 = 3).

x111

H11

Temperature sensor error:
Temperature inside the controller

Sensor for detecting the internal
temperature indicates undefined
values.

l

Contact Lenze.

l

Switch off the monitoring
(C0588 = 3).

x153

P03

Following error

The angle difference between set
and actual position is larger than
the following error limit set under
C0255.

l

Increase following error limit
under C0255.

l

Switch off the monitoring
(C0589 = 3).

Drive cannot follow the digital
frequency (I

max

limit).

Check drive dimensioning.

x163

P13

Angle overrun.

l

Phase controller limit reached

l

Drive cannot follow the digital
frequency (I

max

limit).

l

Enable drive

l

Check drive dimensioning.

x166

P16

Faulty transfer of system bus
(CAN) sync telegram.

The sync telegram from the
master (PLC) is out of sync cycle.

l

Set the "sync cycle" to the
transmission cycle of the
master (PLC) under C1121.

l

Note:
– C0362 displays the time

interval between 2 sync
telegrams.

– C0362 = 0: communication

interrupted.

The sync telegram of the master
(PLC) is not received.

l

Check communication channel.

l

Check baud rate, controller
address.

l

Note:
– C0362 displays the time

interval between 2 sync
telegrams.

– C0362 = 0: communication

interrupted.

The controller is enabled too fast.

Delay the controller enable.
The time delay required depends
on the time interval between the
sync telegrams.