Wiring of the standard device

Important notes
Protection of persons

5

5.1
5.1.1

l

5.1−2

EDSVS9332S EN 6.0−07/2013

The terminals X1 and X5 have double (reinforced) insulation according to
EN50178. The protection against accidental contact is ensured without
additional measured being taken.

{

Danger!

ƒ

The terminals X3, X4, X6, X7, X8, X9, X10, X11 have basic
insulation (single isolating distance).

ƒ

In the event of a defective isolating distance, protection
against accidental contact can only be guaranteed by taking
external measures such as double insulation.

ƒ

If an external DC 24 V voltage source is used, the insulation
degree of the controller depends on the insulation degree of
the voltage source.

59 39 A1 A2 A3 A4 E1 E2 E3 E4 E5

ST1 ST2

28

L1

24 VDC

N

X1

X5

X3 X4 X6 X7 X8 X9 X10 X11

W

V

U

PE

PE

L1

L2

L3

+U

G

-U

G

9300std084

Fig. 5.1−1

Electrical isolation between power terminals, control terminals and housing

Double (reinforced) insulation
Basic insulation

Only replace defective fuses in the deenergised state to the type specified.

Only carry out the safety−related disconnection of the controller from the
mains via a contactor on the input side or a manually operated toggle switch.

Electrical isolation

Replacing defective fuses

Disconnecting the controller
from the mains