Commissioning

Switch−on sequence

6

6.3

l

6.3−1

EDSVS9332S EN 6.0−07/2013

6.3

Switch−on sequence

Switch−on sequence

Note

1.

Ensure that controller inhibit is active after mains
connection.

misc008

59

28

X5

}

Terminal X5/28 = LOW

2.

Ensure that no external error is pending.

Terminal X5/E4 = HIGH

3.

Switch on controller.

A

The control card is operated via an external voltage
supply:
Switch on the external DC 24 V supply voltage.

ON

misc002

B

The control card is operated via an internal voltage
supply:
Switch on the mains. The controller provides the DC
24 V supply.

4.

After approx. 2 s the controller has initialised.

5.

Switch on the PC and start GDC.

GDC starts in the online mode if the PC
and the controller are connected.
Information on the connection
establishment can be found in the
"Global Drive Control (GDC) − Getting
started" manual.

6.

Enter the machine parameters in GDC.

A

Select the basic configuration.
Lenze setting: C0005 = 1000 (basic configuration
˜speed control˜).

^ 6.5−2

B

Adapt the controller to the mains.

^ 6.5−2

C

Enter motor data.

^ 6.5−3

D

Set temperature monitoring of the motor.

Motor with PTC or thermal contact:

^ 6.5−14
Motor with KTY:

^ 6.5−15

E

Select feedback system.

^ 6.6−1

7.

If required, carry out a current controller
adjustment.

^ 6.7−1

8.

If required, carry out a rotor position adjustment.

^ 6.8−1

9.

Configure the function of the control terminals to
adapt them to your application.

If an internal voltage supply is used,
assign X5/x with "FIXED1" and X6/x
with "FIXED100%".

^ 6.9−1

10.

Save the settings with mains failure protection in
one of the 4 parameter sets (C0003).
With C0003 = 1 the settings are saved in parameter
set 1.

After connecting the DC 24 V supply or
after mains connection, parameter set
1 is activated automatically.
(See chapter "Parameterisation")

11.

Switch on the mains if previously only the external
DC 24 V supply voltage was switched on.

12.

Enable controller.

misc009

59

28

X5

}

Terminal X5/28 = HIGH
(see chapter "Commissioning"

®"Controller inhibit")

13.

Define setpoint.

Analog setpoint
selection:
−10 ... +10 V via
potentiometer at X6/1
and X6/2

Fixed speed:
Activate JOG 1 with
X5/E3 = HIGH

JOG 1 is parameterised in C0039/1.