Wiring of the standard device

Standard devices in the power range 15 ... 30 kW
Motor connection

5

5.5
5.5.6

l

5.5−8

EDSVS9332S EN 6.0−07/2013

PE U

V

W

T1 T2

+UG -UG

PES

PES

PE

M

3~

J>

PES

PES

PES

2.7 k

MONIT-OH8

15 V

3.3 k

7.4 k

9300vec139

Fig. 5.5−4

Circuit diagram of motor connection with PTC thermistor or thermal contact (NC
contact) at T1, T2

Characteristics of the connection for motor temperature monitoring:

Terminals T1, T2

Connection

l

PTC thermistor
– PTC thermistor with defined tripping temperature (acc. to

DIN 44081 and DIN 44082)

l

Thermal contact (NC contact)
– Thermostat as NC contact

Tripping point

l

Fixed (depending on the PTC/thermal contact)

l

PTC: R

J

>

1600

W

l

Configurable as warning or error (TRIP)

Notes

l

Monitoring is not active in the Lenze setting.

l

If you do not use a Lenze motor, we recommend the use of a PTC
thermistor up to 150°C.