Motor connection, Wiring of the standard device, Stop – Lenze EVS9332xS User Manual

Page 114: Danger

Advertising
background image

Wiring of the standard device

Standard devices in the power range 15 ... 30 kW

Motor connection

5

5.5

5.5.6

l

5.5−7

EDSVS9332S EN 6.0−07/2013

5.5.6

Motor connection

)

Note!

ƒ

Fusing the motor cable is not required.

ƒ

The drive controller features 2 connections for motor
temperature monitoring:
– Terminals T1, T2 for connecting a PTC thermistor or thermal

contact (NC contact).

– Pins X8/5 and X8/8 of the incremental encoder input (X8) for

connecting a KTY thermal sensor.

(

Stop!

Do not use lugs as strain relief.

PE

T1

T2

U

V

W

a

3.4 Nm
30 lb-in

a

0

9300vec131

Fig. 5.5−3

Installation of shield sheet for drive controllers 15 ... 30 kW

0 Fasten the shield sheet with two self−tapping screws Ж 4 Ч 14 mm (a)

Wire T1, T2 only if the motor is equipped with a PTC thermistor or thermal
contact (NC contact).

ƒ An "open" cable acts like an antenna and can cause faults on the drive

controller.

{

Danger!

ƒ

All control terminals only have basic insulation (single
isolating distance) after connecting a PTC thermistor or a
thermal contact.

ƒ

Protection against accidental contact in case of a defective
isolating distance is only guaranteed through external
measures, e.g. double insulation.

Shield sheet installation

Motor with PTC thermistor or
thermal contact (NC contact)