Commissioning

Current controller adjustment

6

6.7

l

6.7−3

EDSVS9332S EN 6.0−07/2013

0

1

9300std091

9300std092

Fig. 6.7−2

Current characteristic for non−optimum controller adjustment

0 Current rise of motor current too slow

Reset time T

n

(C0076) too long and/or gain V

p

(C0075) too small

Measured at time base 200

ms/DIV

1 High−frequency oscillations of motor current, motor noises may occur

Reset time T

n

(C0076) too short and/or gain V

p

(C0075) too large

Measured at time base 200

ms/DIV

8. Check the transient response over a longer period of time (e.g. with

time base 4000

ms/DIV). The motor current must reach the final

steady−state value within the shortest possible time.

0

1

9300std093

Fig. 6.7−3

Transient response of motor current over longer period of time

0 Optimum transient response

1 Final steady−state value is reached too slowly

Measured at time base 4000

ms/DIV

9. When the current controller adjustment is completed, reset the

temporary settings:
– Set the initial values again in C0006, C0022 and C0025. If necessary,

reconnect the encoder cable to X8.

– Connect the inputs MCTRL−M−ADD and MCTRL−N−SET with the initial

signals.