Changing the assignment of the control terminals X5 and X6

Free configuration of analog input signals

6

6.9

6.9.3

l

6.9−3

EDSVS9332S EN 6.0−07/2013

6.9.3

Free configuration of analog input signals

ƒ Internal analog signals can be freely linked with external analog signal

sources:
– Analog inputs X3/1, X3/2 and X3/3, X3/4

ƒ One signal source can be linked with several targets.

The internal analog signals can be linked with an external signal source by
entering the selection figure of the external signal into the configuration
code of the internal analog signal.

Example

ƒ C0780 = 50

ð signal source for the main setpoint (NSET−N) is terminal

X6/1, X6/2

NSET

C0046

NSET-N

DMUX

0

3

0

15

NSET-JOG*1
NSET-JOG *2
NSET-JOG *4
NSET-JOG *8

C0780

C0787/1

C0787/2
C0787/3
C0787/4

C0034

1

2

AIN1

+

+

AIN1-OUT

AIN1-GAIN

AIN1-OFFSET

C0404/1

C0404/2

C0402

C0403

C0400

X6

C0010

+

+

9300vec106

Fig. 6.9−2

Linking analog signal NSET−N with terminal X6/1, X6/2

I

Tip!

ƒ

A list with all selection figures is included in the chapter
"Configuration"

® "Selection lists".

ƒ

For signal linkage we recommend the function block editor in
GDC (ESP−GDC2).

Gain and offset

Set gain (C0027) and offset (C0026) to adapt the input signal to the
application.

Input range of X6/1, X6/2

Input range

C0034

Position of jumper at X3

−10 V ... +10 V

C0034 = 0

6

4

2

5

3

1

+4 mA ... +20 mA

C0034 = 1

6

4

2

5

3

1

−20 mA ... +20 mA

C0034 = 2

)

Note!

Different settings in C0034 and of X3 result in a wrong input
signal.

Description

Linking signals

Adjustment