Wiring of the standard device – Lenze EVS9332xS User Manual
Page 129
Advertising
![background image](/manuals/566123/129/background.png)
Wiring of the standard device
Standard devices with a power of 45 kW
Motor connection
5.6
5.6.6
l
5.6−10
EDSVS9332S EN 6.0−07/2013
T1
T2
PE
U
V
W
2
3
0
1
U, V, W,
PE
M8
15 Nm
132 lb-in
}
+
PE
M5 x 12
3 Nm (26.5 lb-in)
9300vec124
Fig. 5.6−6
Motor connection with KTY thermal sensor
0 PE stud
PE cable connection with ring cable lug
1 U, V, W
Motor cable connection
Check the correct polarity. Observe maximum length of the motor cable.
Max. connectable cable cross−section: 120 mm
2
with ring cable lug
2 Shield clamps
Place shields of motor cable with large surface on the shield sheet and
fasten with shield clamps and M5 × 12 mm screws
3 Cable ties
Strain relief of motor cable
Advertising
This manual is related to the following products: