Safety instructions

Safety instructions for the installation according to UL

2

2.4

l

2.4−3

EDSVS9332S EN 6.0−07/2013

2.4

Safety instructions for the installation according to UL

J

Warnings!

ƒ

Motor Overload Protection
– For information on the protection level of the internal

overload protection for a motor load, see the corresponding
manuals or software helps.

– If the integral solid state motor overload protection is not

used, external or remote overload protection must be
provided.

ƒ

Branch Circuit Protection
– The integral solid state protection does not provide branch

circuit protection.

– Branch circuit protection has to be provided externally in

accordance with corresponding instructions, the National
Electrical Code and any additional codes.

ƒ

Please observe the specifications for fuses and
screw−tightening torques in these instructions.

ƒ

EVS9321 … EVS9326:
– Suitable for use on a circuit capable of delivering not more

than 5000 rms symmetrical amperes, 480 V maximum,
when protected by fuses.

– Suitable for use on a circuit capable of delivering not more

than 50000 rms symmetrical amperes, 480 V maximum,
when protected by CC, J, T or R class fuses.

– Maximum surrounding air temperature: 0 ... +55 °C
– > +40 °C: reduce the rated output current by 2.5 %/°C
– Use 75 °C copper wire only.

ƒ

EVS9327 … EVS9329:
– Suitable for use on a circuit capable of delivering not more

than 5000 rms symmetrical amperes, 480 V maximum,
when protected by fuses.

– Suitable for use on a circuit capable of delivering not more

than 50000 rms symmetrical amperes, 480 V maximum,
when protected by J, T or R class fuses.

– Maximum surrounding air temperature: 0 ... +50 °C
– > +40 °C: reduce the rated output current by 2.5 %/°C
– Use 60/75 °C or 75 °C copper wire only.