General data and operating conditions, Technical data – Lenze EVS9332xS User Manual

Page 38

Advertising
background image

Technical data

General data and operating conditions

3

3.1

l

3.1−1

EDSVS9332S EN 6.0−07/2013

3.1

General data and operating conditions

Conformity and approval

Conformity

CE

2006/95/EC

Low−Voltage Directive

2004/108/EG

EMC Directive

Approval

UL

cULus

Power Conversion Equipment (File No. E132659)

Protection of persons and equipment

Type of protection

EN 60529

IP20

IP41 in case of thermally separated installation
(push−through technique) between the control
cabinet (inside) and the environment.

NEMA 250

Protection against accidental contact in accordance
with type 1

Earth leakage current IEC/EN 61800−5−1 > 3.5 mA

Observe regulations and
safety instructions!

Insulation of control
circuits

EN 61800−5−1

Safe mains isolation by double (reinforced)
insulation for terminals X1 and X5.
Basic insulation (single isolating distance) for
terminals X3, X4, X6, X7, X8, X9, X10 and X11.

Insulation resistance

IEC/EN 61800−5−1 < 2000 m site altitude: overvoltage category III

> 2000 m site altitude: overvoltage category II

Protective measures

Against short circuit, earth fault (earth−fault
protected during mains connection, limited
earth−fault protection during operation),
overvoltage, motor overtemperature (input for PTC
or thermal contact)

EMC

Noise emission

IEC/EN 61800−3

Cable−guided, up to 10 m motor cable length with
mains filter A: category C2.

Radiation, with mains filter A and installation in
control cabinet: category C2

Interference
immunity

IEC/EN 61800−3

Category C3

Ambient conditions

Climatic

Storage

IEC/EN 60721−3−1 1K3 (−25 ... +55 °C)

< 6 months

1K3 (−25 ... +40 °C)

> 6 months
> 2 years: anodise DC bus
capacitors

Transport

IEC/EN 60721−3−2 2K3 (−25 ... +70 °C)

Operation

EVS9321 ...
EVS9326

IEC/EN 60721−3−3 3K3 (0 ... +55 °C)

> +40 °C: reduce the rated output current by
2.5 %/°C.

EVS9327 ...
EVS9332

3K3 (0 ... +50 °C)
> +40 °C: reduce the rated output current by
2.5 %/°C.

Pollution

EN 61800−5−1

Degree of pollution 2

General data

Operating conditions

Advertising
This manual is related to the following products: