Mains choke/mains filter assignment, Wiring of the standard device – Lenze EVS9332xS User Manual

Page 125

Advertising
background image

Wiring of the standard device

Standard devices with a power of 45 kW
Mains choke/mains filter assignment

5

5.6
5.6.5

l

5.6−6

EDSVS9332S EN 6.0−07/2013

Supply conditions

Range

Description

Fuses

l

Only according to UL 248

l

Mains short−circuit current up to 10000 A

rms

: All classes permissible

l

Mains short−circuit current up to 50000 A

rms

: Only classes "J", "T" or "R"

permissible

Cables

l

Only in accordance with UL

l

The cable cross−sections specified in the following apply under the following
conditions:
– Conductor temperature < 60 °C
– Ambient temperature < 40 °C

Observe all national and regional regulations!

9300

Rated fuse current

Cable cross−section

Fuse

L1, L2, L3, PE

Type

[A]

[AWG]

Operation with mains choke/mains filter

EVS9330−xS

100

1

5.6.5

Mains choke/mains filter assignment

9300

Mains choke

Interference voltage category according to EN 61800−3 and motor cable length

Component

Component

Type

C2

max. [m]

C1

max. [m]

EVS9330−xS

ELN3−0038H085

EZN3A0030H110

25

EZN3B0030H110

50

EZN3A0030H110N001

3)

25

E82ZN55334B230

50

3)

For controllers with thermal separation

Installation to UL

Advertising
This manual is related to the following products: