Safety instructions

Safety instructions for the installation according to UL

2

2.4

l

2.4−4

EDSVS9332S EN 6.0−07/2013

ƒ

EVS9330 … EVS9332:
– Suitable for use on a circuit capable of delivering not more

than 10000 rms symmetrical amperes, 480 V maximum,
when protected by fuses.

– Suitable for use on a circuit capable of delivering not more

than 50000 rms symmetrical amperes, 480 V maximum,
when protected by J, T or R class fuses.

– Maximum surrounding air temperature: 0 ... +50 °C
– > +40 °C: reduce the rated output current by 2.5 %/°C
– Use 60/75 °C or 75 °C copper wire only.