Motor operation is unstable.

Drive will not reverse motor direction.

Drive does not power up.

Cause(s)

Indication

Corrective Action

Motor data was incorrectly
entered.

None

1. Correctly enter motor nameplate

data into

P031

,

P032

and

P033

.

2. Enable

A097

[Compensation].

3. Use

A084

[Boost Select] to

reduce boost level.

Cause(s)

Indication

Corrective Action

Digital input is not selected for
reversing control.

None

Check [Digital Inx Sel]

(See

page 3-14)

. Choose correct input

and program for reversing mode.

Digital input is incorrectly
wired.

None

Check input wiring.

(See page 1-17)

Motor wiring is improperly
phased for reverse.

None

Switch two motor leads.

Reverse is disabled.

None

Check

A095

[Reverse Disable].

Cause(s)

Indication

Corrective Action

No input power to drive.

None

Check the power circuit.

Check the supply voltage.

Check all fuses and disconnects.

Jumper between I/O Terminals
P2 and P1 not installed and/or
DC Bus Inductor not
connected.

None

Install jumper or connect DC Bus
Inductor.