Accel/Decel Selection

The Accel/Decel rate can be obtained by a variety of methods. The
default rate is determined by P039 [Accel Time 1] and P040 [Decel Time
1]. Alternative Accel/Decel rates can be made through digital inputs,
RS485 (DSI) communications and/or parameters. See the chart below
for the override priority.

No

Yes

No

RS485 (DSI) Port

Controls Speed

No

Yes

Drive Stopped
(Not Running)

Yes

Either

P039 [Accel Time 1]/P040 [Decel Time 1]

or

A067 [Accel Time 2]/A068 [Decel Time 2]

can be selected when

RS485 (DSI) port is active.

Input is programmed

as "Accel 2 & Decel 2"

A051, A052, A053

or A054 = 1

No

Yes

A067 [Accel Time 2]/A068 [Decel Time 2]

is active when input is active.

Speed is controlled

by [Preset Freq x]

No

Yes

P039 [Accel Time 1]/P040 [Decel Time 1];

A067 [Accel Time 2]/A068 [Decel Time 2]

determined by the active

Preset Frequency.

See A070-A077 [Preset Freq 0-7]

Either

P039 [Accel Time 1]/P040 [Decel Time 1]

or

A067 [Accel Time 2]/A068 [Decel Time 2]

can be selected by the Digit 3 setting

of the Step Logic parameters.

See A140-A147 [Stp Logic 0-7]

Speed is controlled

by Stp Logic

No

Yes

P039 [Accel Time 1]/P040 [Decel Time 1]

are used.

Drive will Start and Run

at Jog Speed.

Drive will use A079 [Jog Accel/Decel]

Jog Input

Enabled and Active:

A051, A052, A053

or A054 = 2, 11,12