Trim control – Rockwell Automation 22B PowerFlex 40 FRN 1.xx - 6.xx User Manual

Page 147

Advertising
background image

PID Set Up

F-3

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual

Publication 22B-UM001H-EN-E

Trim Control

In Trim Control, the PID Output is added to the Speed Reference. In
Trim mode, the output of the PID loop bypasses the accel/decel ramp as
shown. Trim Control is used when A132 [PID Ref Sel] is set to option 5,
6, 7 or 8.

Example

In a winder application, the PID Reference equals the Equilibrium
set point.

The Dancer Pot signal provides PID Feedback to the drive.
Fluctuations in tension result in a PID Error value.

The Master Speed Reference sets the wind/unwind speed.

As tension increases or decreases during winding, the Speed
Reference is trimmed to compensate. Tension is maintained near the
Equilibrium set point.

+

PID Prop Gain

PID Loop

PID Integ Time

PID Diff Rate

PID Enabled

P038 [Speed Reference]

PID Fdbk

PID Ref

PID

Error

+

+

+

+

PID

Output

Output

Freq

+

Accel/Decel

Ramp

P038 [Speed Reference]

0 Volts

PID Feedback =
Dancer Pot Signal

10 Volts

PID Reference =

Equilibrium Set Point

22B-UM001.book Page 3 Wednesday, January 22, 2014 11:04 AM

Advertising