Advanced Program Group

(continued)

A100 [Fault Clear]

Stop drive before changing this parameter.

Resets a fault and clears the fault queue. Used primarily to clear a fault over network
communications.

Options

0 “Ready/Idle” (Default)

1 “Reset Fault”

2 “Clear Buffer”

(Parameters

d007

-

d009

[Fault x Code])

A101 [Program Lock]

Protects parameters against change by unauthorized personnel.

Options

0 “Unlocked” (Default)

1 “Locked”

A102 [Testpoint Sel]

Related Parameter(s):

d019

Used by Rockwell Automation field service personnel.

Values

Default:

400

Min/Max:

0/FFFF

Display:

1 Hex

A103 [Comm Data Rate]

Related Parameter(s):

d015

Sets the serial port rate for the RS485 (DSI) port.

Important: Power to drive must be cycled before any changes will affect drive operation.

Options

0 “1200”

1 “2400”

2 “4800”

3 “9600” (Default)

4 “19.2K”

5 “38.4K”

A104 [Comm Node Addr]

Related Parameter(s):

d015

Sets the drive node address for the RS485 (DSI) port if using a network connection.

Important: Power to drive must be cycled before any changes will affect drive operation.

Values

Default:

100

Min/Max:

1/247

Display:

1