Advanced Program Group

(continued)

A140 [Stp Logic 0]
A141 [Stp Logic 1]
A142 [Stp Logic 2]
A143 [Stp Logic 3]
A144 [Stp Logic 4]
A145 [Stp Logic 5]
A146 [Stp Logic 6]
A147 [Stp Logic 7]

Related Parameter(s):

P038

,

P039

,

P040

,

A051

-

A054

,

A055

,

A058

,

A061

,

A067

,

A068

,

A070

-

A077

,

A150

-

A157

Values

Default:

00F1

Min/Max:

0001/bAFF

Display:

4 Digits

Parameters A140-A147 are only active if

P038

[Speed Reference] is set to 6 “Stp Logic”.

These parameters can be used to create a custom profile of frequency commands. Each “step” can
be based on time, status of a Logic input or a combination of time and the status of a Logic input.
Digits 0-3 for each [Stp Logic x] parameter must be programmed according to the desired profile.
A Logic input is established by setting a digital input, parameters

A051

-

A054

[Digital Inx Sel], to 23

“Logic In1” and/or 24 “Logic In2”.
A time interval between steps can be programmed using parameters

A150

-

A157

[Stp Logic Time x].

See the table below for related parameters.
The speed for any step is programmed using parameters

A070

-

A077

[Preset Freq x].

How StepLogic Works
The StepLogic sequence begins with a valid start command. A normal sequence always begins with
A140 [Stp Logic 0].
Digit 0: Logic For Next Step
This digit defines the logic for the next step. When the condition is met the program advances to the
next step. Step 0 follows Step 7. Example: Digit 0 is set 3. When “Logic In2” becomes active, the
program advances to the next step.
Digit 1: Logic to Jump to a Different Step
For all settings other than F, when the condition is met, the program overrides Digit 0 and jumps to the
step defined by Digit 2.
Digit 2: Different Step to Jump
When the condition for Digit 1 is met, the Digit 2 setting determines the next step or to end the program.

Stop drive before changing this parameter.

StepLogic Parameter

(Active when P038 = 6 “Stp Logic”)

Related Preset Frequency Parameter

(Can be activated independent of

StepLogic Parameters)

Related StepLogic Time Parameter

(Active when A140-A147 Digit 0 or 1

are set to 1, b, C, d or E)

A140 [Stp Logic 0]

A070 [Preset Freq 0]

A150 [Stp Logic Time 0]

A141 [Stp Logic 1]

A071 [Preset Freq 1]

A151 [Stp Logic Time 1]

A142 [Stp Logic 2]

A072 [Preset Freq 2]

A152 [Stp Logic Time 2]

A143 [Stp Logic 3]

A073 [Preset Freq 3]

A153 [Stp Logic Time 3]

A144 [Stp Logic 4]

A074 [Preset Freq 4]

A154 [Stp Logic Time 4]

A145 [Stp Logic 5]

A075 [Preset Freq 5]

A155 [Stp Logic Time 5]

A146 [Stp Logic 6]

A076 [Preset Freq 6]

A156 [Stp Logic Time 6]

A147 [Stp Logic 7]

A077 [Preset Freq 7]

A157 [Stp Logic Time 7]