RS485 (DSI) Protocol

C-5

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual

Publication 22B-UM001H-EN-E

Writing (06) Reference

The Speed Reference to a PowerFlex 40 drive can be controlled via the
network by sending Function Code 06 writes to register address 8193
(Reference). P038 [Speed Reference] must be set to 5 “RS485 (DSI)
Port” in order to accept the Speed Reference.

In addition to being written, register address 8193 can be read using
Function Code 03.

Reading (03) Logic Status Data

The PowerFlex 40 Logic Status data can be read via the network by
sending Function Code 03 reads to register address 8448 (Logic Status).

Reference

Address (Decimal)

Description

8193

A decimal value entered as xxx.x where the decimal point is fixed. For
example, a decimal “100” equals 10.0 Hz and “543” equals 54.3 Hz.

Logic Status

Address (Decimal)

Bit(s)

Description

8448

0

1 = Ready, 0 = Not Ready

1

1 = Active (Running), 0 = Not Active

2

1 = Cmd Forward, 0 = Cmd Reverse

3

1 = Rotating Forward, 0 = Rotating Reverse

4

1 = Accelerating, 0 = Not Accelerating

5

1 = Decelerating, 0 = Not Decelerating

6

1 = Alarm, 0 = No Alarm

7

1 = Faulted, 0 = Not Faulted

8

1 = At Reference, 0 = Not At Reference

9

1 = Reference Controlled by Comm

10

1 = Operation Cmd Controlled by Comm

11

1 = Parameters have been locked

12

Digital Input 1 Status

13

Digital Input 2 Status

14

Digital Input 3 Status

(1)

(1)

This status is available only with firmware revision FRN 2.xx and higher.

15

Digital Input 4 Status

(1)

22B-UM001.book Page 5 Wednesday, January 22, 2014 11:04 AM