Fault descriptions, Fault descriptions -3, R to – Rockwell Automation 22B PowerFlex 40 FRN 1.xx - 6.xx User Manual

Page 95: Chapter 4, Motor overload, Auxiliary input, Table 4.a

Advertising
background image

Troubleshooting

4-3

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual

Publication 22B-UM001H-EN-E

Table 4.A Fault Types, Descriptions and Actions

Fault Descriptions

No.

Fault

Type

(1

)

Description

Action

F2

Auxiliary Input

Auxiliary input interlock is open.

1. Check remote wiring.
2. Verify communications

programming for intentional fault.

F3

Power Loss

Excessive DC Bus voltage ripple. 1. Monitor the incoming line for

phase loss or line imbalance.

2. Check input line fuse.

F4

UnderVoltage

DC bus voltage fell below the
minimum value.

Monitor the incoming AC line for low
voltage or line power interruption.

F5

OverVoltage

DC bus voltage exceeded
maximum value.

Monitor the AC line for high line
voltage or transient conditions. Bus
overvoltage can also be caused by
motor regeneration. Extend the
decel time or install dynamic brake
option.

F6

Motor Stalled

Drive is unable to accelerate
motor.

Increase

P039

-

A067

[Accel Time x]

or reduce load so drive output
current does not exceed the current
set by parameter

A089

[Current

Limit 1].

F7

Motor Overload

Internal electronic overload trip.

1. An excessive motor load exists.

Reduce load so drive output
current does not exceed the
current set by parameter

P033

[Motor OL Current].

2. Verify

A084

[Boost Select]

setting

F8

Heatsink
OvrTmp

Heatsink temperature exceeds a
predefined value.

1. Check for blocked or dirty heat

sink fins. Verify that ambient
temperature has not exceeded
40

°

C (104

°

F) for IP30, NEMA UL

Type 1 installations or 50°C (122°F)
for IP20/Open type installations.

2. Check fan.

F12

HW OverCurrent

The drive output current has
exceeded the hardware current
limit.

Check programming. Check for
excess load, improper

A084

[Boost

Select] setting, DC brake volts set
too high or other causes of excess
current.

F13

Ground Fault

A current path to earth ground
has been detected at one or
more of the drive output
terminals.

Check the motor and external wiring
to the drive output terminals for a
grounded condition.

F29

Analog Input
Loss

An analog input is configured to
fault on signal loss. A signal loss
has occurred.
Configure with

A122

[Analog In

Loss].

1. Check parameters.
2. Check for broken/loose

connections at inputs.

22B-UM001.book Page 3 Wednesday, January 22, 2014 11:04 AM