1-16

Installation/Wiring

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual
Publication 22B-UM001H-EN-E

Figure 1.5 Control Wiring Block Diagram

(1)

Important: I/O Terminal 01 is always a coast to stop
input except when P036 [Start Source] is set to
“3-Wire” or “Momt FWD/REV” control. In three wire
control, I/O Terminal 01 is controlled by P037 [Stop
Mode]. All other stop sources are controlled by P037
[Stop Mode].
Important: The drive is shipped with a jumper installed between I/O Terminals 01 and 11. Remove
this jumper when using I/O Terminal 01 as a stop or enable input.

(2)

Two wire control shown. For three wire control use a momentary input

on I/O Terminal 02 to

command a start. Use a maintained input

for I/O Terminal 03 to change direction.

(3)

When using an opto output with an inductive load such as a relay, install a recovery diode parallel
to the relay as shown, to prevent damage to the output.

(4)

When the ENBL enable jumper is removed, I/O Terminal 01 will always act as a hardware enable,
causing a coast to stop without software interpretation.

04

05

06

07

01

02

03

08

09

11

12

13

14

15

16

17

18

19

Digital Common

Digital Input 1

Digital Input 2

Digital Input 3

Stop

(1)(4)

Start/Run FWD

(2)

Direction/Run REV

Digital Input 4

Opto Common

R1

R2

R3

Relay N.O.

Relay Common

Relay N.C.

+24V DC

+10V DC

0-10V (or ±10V) Input

Analog Common

4-20mA Input

Analog Output

Opto Output 1

Opto Output 2

RS485 Shield

+24V

+10V

Typical

SNK Wiring

Typical

SRC Wiring

1

RS485

(DSI)

R1 R2 R3

SNK

SRC

0-10V

0-20mA

01 02 03 04 05

11 12 13 14 15

06 07 08 09

16 17 18 19

(1)

Enable Jumper

(4)

30V DC
50mA
Non-inductive

Common

24V

ENBL

Enable

(4)

Jumper

(3)

Pot must be
1-10k ohm
2 Watt Min.

0-10V

0/4-20mA

Analog Output Select

SRC

SNK

30V DC 125V AC 240V AC

Resistive

3.0A

3.0A

3.0A

Inductive

0.5A

0.5A

0.5A

P036 [Start Source]

Stop

I/O Terminal 01 Stop

Keypad

Per P037

Coast

3-Wire

Per P037

Per P037

(4)

2-Wire

Per P037

Coast

Momt FWD/REV

Per P037

Per P037

(4)

RS485 Port

Per P037

Coast

22B-UM001.book Page 16 Wednesday, January 22, 2014 11:04 AM