Programming and Parameters

3-13

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual

Publication 22B-UM001H-EN-E

Basic Program Group

(continued)

P040 [Decel Time 1]

Related Parameter(s):

P038

,

P039

,

A051

-

A054

,

A068

,

A070

-

A077

,

A140

-

A147

Sets the rate of deceleration for all speed decreases.

Values

Default:

10.0 Secs

Min/Max:

0.1/600.0 Secs

Display:

0.1 Secs

Maximum Freq

Decel Time

Decel Rate

=

Speed

0

Time

P035 [Maximum Freq]

P039 or A067
[Accel Time x]

P040 or A068

[Decel Time x]

0

Acceler

ation

Deceler

ation

P041 [Reset To Defalts]

Stop drive before changing this parameter.

Resets all parameter values to factory defaults.

Options

0 “Ready/Idle” (Default)

1 “Factory Rset”

After the reset function is complete, this parameter will set
itself back to “0”.

Causes an F48

Params Defaulted

fault.

P042 [Voltage Class]

Stop drive before changing this parameter.

Sets the voltage class of 600V drives.

Options

2 “Low Voltage”

480V

3 “High Voltage”

(Default)

600V

P043 [Motor OL Ret]

Related Parameter(s):

P033

Enables/disables the Motor Overload Retention function. When Enabled, the value held in the motor
overload counter is saved at power-down and restored at power-up. A change to this parameter
setting resets the counter.

Options

0 “Disabled” (Default)

1 “Enabled”