A056, T in – Rockwell Automation 22B PowerFlex 40 FRN 1.xx - 6.xx User Manual

Page 63

Advertising
background image

Programming and Parameters

3-17

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual

Publication 22B-UM001H-EN-E

A055
Options
(Cont.)

19 “Anlg In Loss”

Analog input loss has occurred. Program

A122

[Analog In

Loss] for desired action when input loss occurs.

20 “ParamControl”

Prior to FRN 4.01, this option enables the output to be
controlled over network communications by writing to

A056

[Relay Out Level]. (0 = Off, 1 = On.)

With FRN 4.01 and later, the logic command word bit 15 has
full control of

A056

. See

Writing (06) Logic Command

Data on page C-4

.

21 “NonRec Fault”

Value set in

A092

[Auto Rstrt Tries] is exceeded.

A092

[Auto Rstrt Tries] in not enabled.

A Non-resettable fault has occurred.

22 “EM Brk Cntrl”

EM brake is energized. Program

A160

[EM Brk Off Delay] and

A161

[EM Brk On Delay] for desired action.

23 “Above Fcmd”

The current commanded frequency exceeds the value set in

A056

[Relay Out Level].

24 “MsgControl”

With FRN 4.01 and later, this option enables the output to be
controlled over network communications by writing to

A056

[Relay Out Level]. (0 = Off, 1 = On.)

A056 [Relay Out Level]

Related Parameter(s):

A055

32 bit parameter.

Sets the trip point for the digital output relay if the value of

A055

[Relay Out Sel] is 6, 7, 8, 10, 16, 17,

18 or 20.
With FRN 4.01 and later, when the value of

A055

is set to 20, the logic command word bit 15 has full

control of A056.

Values

Default:

0.0

Min/Max:

0.0/9999

Display:

0.1

32

A055 Setting

A056 Min/Max

6
7
8
10
16
17
18
20
23

0/400 Hz
0/180%
0/815 Volts
0/100%
0.1/9999 Secs
1/9999 Counts
1/180 degs
0/1
0/400 Hz

22B-UM001.book Page 17 Wednesday, January 22, 2014 11:04 AM

Advertising