Analog pid reference signals, Scale function, Analog pid reference signals . . . . . . . . . f-5 – Rockwell Automation 22B PowerFlex 40 FRN 1.xx - 6.xx User Manual

Page 149

Advertising
background image

PID Set Up

F-5

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual

Publication 22B-UM001H-EN-E

Analog PID Reference Signals

Parameters A110 [Anlg In 0-10V Lo] and A111 [Anlg In 0-10V Hi] are
used to scale or invert an analog PID Reference.

Important: Firmware version FRN 2.xx also allows PID Feedback

scaling from an analog input.

Examples

Scale Function

For a 0-5 volt signal, the following parameter settings are used so that a 0
volt signal = 0% PID Reference and a 5 volt signal = 100% PID
Reference.

A110 [Anlg In 0-10V Lo] = 0.0%

A111 [Anlg In 0-10V Hi] = 50.0%

A132 [PID Ref Sel] = 0 “0-10V Input”

0

10

20

30

40

50

60

70

80

90 100

PID Reference (%)

Input V

olts

2

4

6

8

10

12

22B-UM001.book Page 5 Wednesday, January 22, 2014 11:04 AM