A080, A081, A079 – Rockwell Automation 22B PowerFlex 40 FRN 1.xx - 6.xx User Manual

Page 70: Advanced program group, Continued)

Advertising
background image

3-24

Programming and Parameters

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual
Publication 22B-UM001H-EN-E

Advanced Program Group

(continued)

A079 [Jog Accel/Decel]

Related Parameter(s):

A078

,

A051

-

A054

Sets the acceleration and deceleration time when a jog command is issued.

Values

Default:

10.0 Secs

Min/Max:

0.1/600.0 Secs

Display:

0.1 Secs

A080 [DC Brake Time]

Related Parameter(s):

P037

,

A081

Sets the length of time that DC brake current is “injected” into the motor. Refer to parameter

A081

[DC

Brake Level].

Values

Default:

0.0 Secs

Min/Max:

0.0/99.9 Secs (A setting of 99.9 = Continuous)

Display:

0.1 Secs

A081 [DC Brake Level]

Related Parameter(s):

P037

,

A080

Defines the maximum DC brake current, in amps, applied to the motor when

P037

[Stop Mode] is set

to either “Ramp” or “DC Brake”.

Values

Default:

Drive Rated Amps

×

0.05

Min/Max:

0.0/(Drive Rated Amps

×

1.8)

Display:

0.1 Amps

P037 DC Injection Braking Mode

Volts/Speed

Voltage

Time

Stop Command

Speed

[DC Brake Level]

[DC Brake Time]

Volts/Speed

P037 Ramp-to-Stop Mode

Time

Stop Command

[DC Brake Level]

[DC Brake Time]

Voltage

Speed

!

ATTENTION:

If a hazard of injury due to movement of equipment or material exists,

an auxiliary mechanical braking device must be used.

!

ATTENTION:

This feature should not be used with synchronous or permanent

magnet motors. Motors may be demagnetized during braking.