PID Set Up

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual
Publication 22B-UM001H-EN-E

Invert Function

For a 4-20mA signal, the following parameter settings are used so that a
20mA signal = 0% PID Reference and a 4mA signal = 100% PID
Reference.

A112 [Anlg In 4-20mA Lo] = 100.0%

A113 [Anlg In 4-20mA Hi] = 0.0%

A132 [PID Ref Sel] = 3 “4-20mA Input”

Alternatively, you can set the value of A167 [PID Invert Error] to 1 to
change the sign of the PID error. See

A167

[PID Invert Error] in Chapter

3 for more details.

PID Deadband

Parameter A138 [PID Deadband] is used to set a range, in percent, of the
PID Reference that the drive will ignore.

Example

[PID Deadband] is set to 5.0

The PID Reference is 25.0%

The PID Regulator will not act on a PID Error that falls between 20.0
and 30.0%

0

10

20

30

40

50

60

70

80

90 100

PID Reference (%)

4-20mA

Input

4

8

12

16

20

24