A070, A077, A078 – Rockwell Automation 22B PowerFlex 40 FRN 1.xx - 6.xx User Manual

Page 69: Advanced program group, Continued), A070 [preset freq 0, A078 [jog frequency

Advertising
background image

Programming and Parameters

3-23

PowerFlex 40 Adjustable Frequency AC Drive FRN 1.xx - 6.xx User Manual

Publication 22B-UM001H-EN-E

Advanced Program Group

(continued)

A070 [Preset Freq 0]

(1)

A071 [Preset Freq 1]
A072 [Preset Freq 2]
A073 [Preset Freq 3]
A074 [Preset Freq 4]
A075 [Preset Freq 5]
A076 [Preset Freq 6]
A077 [Preset Freq 7]

Related Parameter(s):

P038

,

P039

,

P040

,

A051

-

A053

,

A067

,

A068

,

A140

-

A147

,

A150

-

A157

Values

A070 Default:

(1)

A071 Default:
A072 Default:
A073 Default:
A074 Default:
A075 Default:
A076 Default:
A077 Default:

0.0 Hz
5.0 Hz
10.0 Hz
20.0 Hz
30.0 Hz
40.0 Hz
50.0 Hz
60.0 Hz

Min/Max:

0.0/400.0 Hz

Display:

0.1 Hz

Provides a fixed frequency command value when

A051

-

A053

[Digital Inx Sel] is set to 4 “Preset

Frequencies”.
An active preset input will override speed command as shown in the flowchart on page

1-23

.

(1)

To activate A070 [Preset Freq 0] set

P038

[Speed Reference] to option 4 “Preset Freq 0-3”.

Input State

of Digital In 1

(I/O Terminal 05

when A051 = 4)

Input State

of Digital In 2

(I/O Terminal 06

when A052 = 4)

Input State

of Digital In 3

(I/O Terminal 07

when A053 = 4)

Frequency Source

Accel / Decel Parameter Used

(2)

0

0

0

A070 [Preset Freq 0]

[Accel Time 1] / [Decel Time 1]

1

0

0

A071 [Preset Freq 1]

[Accel Time 1] / [Decel Time 1]

0

1

0

A072 [Preset Freq 2]

[Accel Time 2] / [Decel Time 2]

1

1

0

A073 [Preset Freq 3]

[Accel Time 2] / [Decel Time 2]

0

0

1

A074 [Preset Freq 4]

[Accel Time 1] / [Decel Time 1]

1

0

1

A075 [Preset Freq 5]

[Accel Time 1] / [Decel Time 1]

0

1

1

A076 [Preset Freq 6]

[Accel Time 2] / [Decel Time 2]

1

1

1

A077 [Preset Freq 7]

[Accel Time 2] / [Decel Time 2]

(2)

When a Digital Input is set to “Accel 2 & Decel 2”, and the input is active, that input overrides the settings in this
table.

A078 [Jog Frequency]

Related Parameter(s):

P035

,

A051

-

A054

,

A079

Sets the output frequency when a jog command is issued.

Values

Default:

10.0 Hz

Min/Max:

0.0/[Maximum Freq]

Display:

0.1 Hz

22B-UM001.book Page 23 Wednesday, January 22, 2014 11:04 AM

Advertising